MR-J3驅(qū)動,QD75MH4定位模塊 控制X,Y,Z三根軸 X電機是3.5KW,Y,Z電機是2KW X,Y電機電纜接反,數(shù)據(jù)線接對 在不知情況下灌進(jìn)PLC和QP 開始只有Z驅(qū)動出現(xiàn)2032錯誤,有時還有2033,2050錯誤 后來Y,Z軸都出現(xiàn)2032錯誤,怎么解決 |
---|---|
|
xyd_hsn10
jakenghuang
級別: 網(wǎng)絡(luò)英雄
|
你是不是很高的計素,為何不用QD75P而用QD75M |
---|---|
|
syking1234
級別: 略有小成
|
錯誤2032 Error code 2032 Error name Overcurrent 1. Current that flew is higher than the permissible current of the servo amplifier. 1) Short occurred in servo motor power (U, V, W). 2) Transistor (IPM) of the servo amplifier faulty. 3) Ground fault occurred in servo motor power (U, V, W). 4) External noise caused the overcurrent detection circuit to mis-operate. Remedy 1. 1),3) remedy Correct the wiring. 1. 2) remedy Change the servo amplifier. 1. 4) remedy Take noise suppression measures. 既然知道錯誤代碼,看QD75軟件里的幫助 |
---|---|
|